Where, how many, and by what standard should gas leak detectors be installed? Korean installation requirements are split across three regulatory regimes — workplace safety, gas facilities, and fire safety — which can be confusing at first. Ace Electronics, a gas detector manufacturer since 1993 and a KOLAS-accredited calibration laboratory, organizes the big picture by regime.
Three regulatory regimes govern installation
Which standard applies depends on the type of facility and the gas being handled.
| Regime | Main basis | Applies to (e.g.) |
|---|---|---|
| Workplace safety | Occupational Safety and Health acts and KOSHA technical guidelines | Plants and laboratories handling chemicals |
| Gas safety | High-pressure gas, LPG, and city gas acts with KGS codes | Gas storage/use facilities, designated gas-using premises |
| Fire safety | Fire safety standards for gas leak alarms | Gas leak alarms in buildings subject to fire codes |
※ More than one regime can apply to a single site. Confirm the exact applicable rules with your authority or safety manager.
Placement — gas density decides
Sensor placement follows whether the target gas is heavier or lighter than air — the sensor must sit where leaked gas accumulates.
| Gas type | Examples | Sensor position |
|---|---|---|
| Heavier than air | LPG (propane, butane) | Near the floor (commonly within 30 cm above it) |
| Lighter than air | City gas (LNG/methane), hydrogen | Near the ceiling (commonly within 30 cm below it) |
Sensors should also sit close to potential leak points (valves, pipe joints, compressors) and away from vents or doorways where airflow disperses gas.
How many, and when should it alarm
- Quantity — under the high-pressure gas codes, the common rule is at least one sensor per 10 m of equipment-group floor perimeter indoors, and per 20 m outdoors.
- Alarm setpoints — the accepted practice is at or below 25% of the lower explosive limit (LEL) for combustible gases, and at or below the permissible exposure level for toxic gases.
- Shutoff interlock — designated gas-using premises such as larger restaurants may be required to install an automatic gas shutoff device that trips on alarm.
※ These figures summarize widely applied rules; details per facility type follow the applicable codes (KGS, KOSHA guidelines, fire safety standards).
Installation is not the end — calibrate to maintain
Even a correctly installed detector drifts over time. Periodic calibration keeps the alarm accurate at its setpoint. See our calibration cycle guide for recommended intervals and the legal basis.